EasyManua.ls Logo

LEYBOLD SCROLLVAC plus - Electrical Supply Connection

LEYBOLD SCROLLVAC plus
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
the 3-phase pump system must be installed with motor thermal overload
protection. Failur
e to install the 3-phase pump system without the specied
motor thermal overload protection could result in permanent damage to the
pump if subjected to sustained overload or fault conditions, e.g. a block
exhaust.
Furthermore, the pump housing surface temperature could reach levels
greater than 105 °C without this protection.
Table 6 Fuses and circuit breakers
Input supply
Rated system input cur‐
rent
Recommended external
fuse rating
Recommended fuse
type
200 V, 50 Hz 2.4 A rms 2.5 A, 250 V a.c
RK1 and RK5
200-230 V, 60 Hz 2.4 A rms 2.5 A, 250 V a.c
380-415 V, 50 Hz 1.5 A rms 1.6 A, 600 V a.c
RK1, RK5 and J
460 V, 60 Hz 1.5 A rms 1.6 A, 600 V a.c
Table 7 Recommended motor thermal overload protection
Parameter 3-phase SCROLLVAC 15, 18, 7 and 10 plus
Supply voltage and frequency
200 V,
50 Hz
200 - 230 V,
60 Hz
380 415 V,
50 Hz
460 V,
60 Hz
Maximum COP current (A rms) 1.85 1.75 1.45 1.30
Maximum Atmospheric current (Arms) 2.15 2.75 1.55 1.50
Motor thermal overload setting (Arms) 2.40 1.50
Recommended motor thermal overload
device
ABB: T16 - 3.1 ABB: T16 - 1.7
Trip class 10
6.7.1Electrical supply connection
CAUTION: PUMP DAMAGE
The 3-phase pump system is delivered congured for high voltage use. High
voltage is dened as: 380 415 V/50 Hz and 460 V/60 Hz. Make sure that the
pump is correctly congured for the electrical supply voltage and frequency. If not,
the embedded 3-phase motor within the pump can be damaged.
The 3-phase pump system is not designed to be powered directly from a variable
speed drive (VSD) using inverter technology. The direct use of inverter technology
will lead to increased heating within the pump system, resulting in long term
damage to the pump.
3-phase power must be connected to the 3-phase pump system. The
overall 3-phase cable must include 3 live wires and a protective earth (PE)
ground wire.
In addition to the primary 3-phase power supply connection to the pump,
the pump must also be earthed via the secondary earth connection on the
front of the pump housing using a M5x10 screw with a shake proof washer,
refer to
 for more details.
The specication of this secondary earth wire must also meet the above
mentioned requirements.
300668736_002_C7 - © Leybold 31
Installation

Table of Contents

Related product manuals