35
Function
Product
Description Option
Air
Conditioner
Ventilation
CO
2
Fan
Control
○
This function sets the FAN
operating standards based on the
CO
2
concentration of ventilation
products.
Fan Control During
Operation On
Fan Control During
Operation Off
Off / Periodic / Low Off / Periodic
Select
Humidication
Range
○
A function to set the room
humidication operation range of
direct-type ventilation product.
Min. humidity Max. humidity
20% ~ 70% 50% ~ 80%
• The min. humidity and the max. humidity can
be changed by 5% at a time.
• The min. humidity and the max. humidity must
be kept different from each other by 10%.
Interlock air
purication
with air
conditioner
and
ventilation
○
AC-ventilation air purication
interlock is a function that aids
with indoor air purication by
operating ventilation with the
air purication operation of the
AC when the indoor ne dust
concentration is bad.
ON / OFF
• If the AC's fine dust concentration is bad or very
bad, ventilation is interlocked.
• Ventilation is operated at Special High Speed
during interlocking operation.
AI Indoor
Space Care
○
A function where nearby indoor
units cooperate to create a
pleasant space when the target
temperature cannot be reached
due to ambient thermal load,
even though 100% of the indoor
unit’s cooling / heating capacity is
being used.
Use (Y / N)
Indoor Space
Search
Group Number
On / Off
Auto
Manual
(Comfort)
Manual
(Saving)
00~FF
• Auto: Automatic space learning
• Manual (Comfort): Set manual group / Set comfort
first
• Manual (Saving): Set manual group / Set power
saving first
NOTE
• AI Indoor Space Care finds surrounding indoor units that can cooperate through AI field learning.
: It needs at least two weeks for the learning period, and additional learning periods may be required depending on the
operation method and environment at the installation site.
• You can operate up to 2 cooperative indoor units.
• After setting to use AI Indoor Space Care, it is available when operating AI Smart Care.
• AI Indoor Space Care indoor units may be automatically turned on and off as a result of AI field learning.
• If you do not wish to use the AI indoor space care operation function, set it to OFF.
• If a model for both cooling / heating, AI Indoor Space Care is not available during simultaneous cooling and heating
operation.