What to do if Liebert UPS show 'External Battery Module Warning'?
- SSamantha SimmonsAug 27, 2025
If your Liebert UPS displays an 'External Battery Module Warning', verify proper connections between the UPS and the Non-Modular Battery Cabinet. Reenter the amp-hour rating for the external battery (set the amp-hour entry to zero and press the return key, then reset it to the appropriate value for the external battery). If the problem persists, the external battery should be replaced.