EasyManua.ls Logo

Liebert NXC 40kVA - CSA of UPS Cable; Selection of UPS I;O Switch; Distance between the UPS Connection Point and the Floor; Notes

Liebert NXC 40kVA
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 Chapter 3 Electrical Installation
Liebert NXC 30kVA And 40kVA UPS User Manual
3.1.3 CSA Of UPS Cable
The minimum CSA of the UPS cable is listed in Table 3-2.
Table 3-2 Min. CSA of the UPS cable (unit: mm
2
, ambient temperature: 25°C)
Model
Input
Output
Bypass
Neutral line
Earth cable
Battery
30kVA (3-in, 3-out)
16
16
16
25
16
35
40kVA (3-in, 3-out)
16
16
16
25
16
35
3.1.4 Selection Of UPS I/O Switch
Table 3-3 is the recommended UPS I/O switch capacity, and the user can select it according to actual needs.
Table 3-3 Selection of the UPS I/O switch
Model Input port
Recommended capacity
of input external switch
BCB
Output
port
Recommended
capacity of output
external switch
30kVA (3-in, 3-out)
Terminal
block
63A (3P), bypass 100A
(3P)
DC 160A (4P)
Terminal
blcok
63A (3P)
40kVA (3-in, 3-out)
Terminal
block
100A (3P), bypass 125A
(3P)
DC 160A (4P)
Terminal
block
100A (3P)
Note: The BCB (125A) is recommended for common input configuration
3.1.5 Distance Between The UPS Connection Point And The Floor
See Table 3-4 for details.
Table 3-4 Min. distance between UPS connection point and floor
UPS connection point
Min. distance
mm
30kVA
40kVA
Rectifier input 345 345
Bypass input 284 284
AC Output 250 250
Battery 994 994
PE terminal 740 740
3.1.6 Notes
The following points are for general guidance only. If there are relevant local regulations, the local regulations shall
prevail.
1. The cable size of the neutral line shall be selected according to 1.5 times of the output/bypass phase current.
2. The cable size of the protective earth cable shall be selected according to the AC power failure level, cable length
and protection type. The grounding wire connection must use the shortest connection route.
3. For the cables with large current, parallel connection of small cables can be adopted to facilitate the installation.
4. When selecting the battery cable size, the current value in Table 3-1 shall be referred to, and a maximum voltage
drop of 4Vdc is allowed.
5. Do not form coils, so as to minimize the formation of EMI.
3.1.7 Power Cable Connecting Terminal
The rectifier input, bypass input, output and battery power cables are connected to the corresponding terminals shown
in Figure 3-2. Protection Ground
The protective earth cable is reliably connected to the PE input terminal (see Figure 3-2) via the fixing bolt. All the
cabinets and cable troughs shall be grounded according to the local regulations. The grounding wires shall be tied up
reliably to prevent the loosening of the grounding wire tightening screws when the grounding wires are pulled.
Warning

Table of Contents

Related product manuals