EasyManua.ls Logo

Liebert NXC 40kVA - Installation Environment and Design

Liebert NXC 40kVA
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36 Chapter 5 UPS Operation Introduction
Liebert NXC 30kVA And 40kVA UPS User Manual
Figure 5-1 UPS power switch
5.2 UPS Startup Procedures
The UPS must be completely installed and tested by authorized engineer, and external power supply switch is closed,
then you can start the UPS.
5.2.1 Startup Procedures In Normal Mode
Warning
1. These procedures result in mains voltage being applied to the UPS output terminals.
2. If any load equipment is connected to the UPS output terminals, check with the user that it is safe to apply power. If the load is
not ready to receive power, please disconnect the downstream load switch, and stick a warning label on the connection point of the
load.
Use the following procedures to turn on the UPS from a fully powered down condition.
1. Open the front door of the UPS, ensure that the internal maintenance bypass switch Q3 is disconnected and switch
Q6 is closed, while the input cables and copper bars are reliably connected.
Warning
All operations relating to disconnect or close the switch of maintenance bypass switch shall be finished within three seconds, in
case of misreporting as faults.
2. Close the bypass input switch Q2, rectifier input switch Q1, output switch Q5 and all external output isolating
switches (if any) of the UPS in turn.
At the moment, the system is power on, and the startup screen pops up. Refer to 4.2.1 Start Screen.
About 25 seconds later, confirm that the LCD shows the rectifier power supply and the bypass power supply are
normal; if not, check whether the switches Q1 and Q2 are closed. Then the rectifier starts up and the alarm indicator
(red) is on. At the same time, the bypass static switch is closed. About 30 seconds later, the alarm indicator (red) is
flashing, and then the rectifier startup is finished.
Neutral line switch Q6
Ouput switch Q5
Maintenance bypass switch Q3
Bypass input switch Q2
Rectifier input switch Q1

Table of Contents

Related product manuals