Chapter 11 Specifications 81
Liebert NXC 30kVA And 40kVA UPS User Manual
Chapter 11 Specifications
This chapter lists the UPS specifications.
11.1 Conformance And Standards
The UPS has been designed to comply with the European and international standards listed in Table 11-1.
Table 11-1 European and international standards
General safety requirements for UPS
EN62040-1/IEC62040-1/AS62040-1
EN62040-2/IEC62040-2/AS62040-2
Method of specifying the performance and test requirements of UPS
EN62040-3/IEC62040-3/AS62040-3 (VFI SS 111)
Note: The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards for safety
(IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series
and 60529)
11.2 Environmental Characteristics
Table 11-2 Environmental characteristics
Item Unit
Noise within 1m (in the front)
≤ 1000 (derate power by 1% per 100m when above 1000m)
0 ~ 40°C (Note: Battery life is halved for every 10°C increase above 20°C)
Storage and transport ation
temperature for UPS
°C -40°C ~ +70°C
11.3 Mechanical Characteristics
Table 11-3 Mechanical characteristics
Item Unit
Dimensions (W × D × H) mm 600 × 850 × 1600
Protection degree, IEC (60529)
IP20 (front door open or closed)