34 Chapter 4 Operator Control And Display Panel
Liebert NXC 30kVA And 40kVA UPS User Manual
Alarm
Explanation
Monitor flash update
Monitoring software being updated
FLASH operate fail
Historical record not saved
Remote turn ON
Turn on the inverter through the service command
Remote turn ON failed
Caused by invalid operation (maintenance bypass switch closed), DC bus or rectifier not ready
Remote turn OFF
Turn off the inverter through the service command
Load sharing abnormal
Each UPS module is parallel system cannot execute load sharing
Communication fail
Interruption in communication between internal monitoring board and inverter, rectifier
Parallel comm. fail
Communication between the UPS modules of a parallel system failed. Check if any UPS modules in the
parallel system are not on; if yes, power on these UPSs and then check if the alarm disappears
No battery
Check the battery and battery connection
Batt. converter fault
Bus voltage abnormal
Battery reverse
Reconnect battery and check battery wiring
Battery period testing
The battery is under automatic periodic battery maintenance test (20% capacity discharge)
Batt. capacity testing
The user initiated a battery capacity test (100% capacity discharge)
Battery maintenance
testing
The user initiated a maintenance test (20% capacity discharge)
Battery end of discharge
Inverter turned off due to battery EOD
Battery overtemp.
The battery temperature is over limit
Replace battery
Battery life is finished
Battery low pre-warning
Before the EOD, battery low pre-warning will occur. After this pre-warning, the battery will have the
capacity for 3min discharging with full load. The time is user-settable from 3min to 6min
Generator in
Dry contact signal, indicating generator connected
BCB status abnormal
Logic conflict between BCB drive signal and feedback signal
BCB closed
BCB state (closed)
BCB open
BCB state (open)
Note:
1. For UPS installed with the optional battery monitor, refer to the user manual of the battery monitor for the alarm messages related
to battery cell and charge current.
2. If the alarm is caused through setting the software value by Emerson authorized engineer, and you wish to change the setting
values, please contact the Emerson local customer service center