84 Chapter 11 Specifications
Liebert NXC 30kVA And 40kVA UPS User Manual
30kVA
40kVA
Efficiency
Normal mode
100% load
%
94.7%
94.4%
75% load
%
94.8%
94.7%
67% load
%
94.8%
94.7%
50% load
%
94.6%
94.8%
33% load
%
93.5%
94.3%
25% load
%
91.7%
93.6%
ECO mode
%
98.4%
98.4%
Loss
Normal mode (no load)
kW
1.116
1.116
Normal mode (full load)
kW
1.620
2.240
Note: 400Vac input and output, battery fully charged, full-rated linear load