Chapter 8 Option Boards and Memory Module
XBC E-Type Main Unit 8-20 Ver. 1
4. Parameter setup
a. Action command
Type
Device status information (based on slot 9, ch0)
Ref.
CH0
Information
Enable counter
U9.0.0
0: disable, 1: enable
BIT
Enable internal preset
U9.0.1
0: disable, 1: enable
BIT
Count inc./dec. flag
U9.0.3
0: INC, 1: DEC
BIT
Latch counter enable
U9.0.6
0: disable, 1: enable
BIT
Pulse input mode U9.5
0: 1-phase 1-input
1: 1-phase 2-input
2: 2-phase 2 multiplication
INT
Internal preset setting value
U9.6
-2,147,483,648 ~ 2,147,483,647
DINT
b. Monitor area
Type
Device status information (based on slot 9, ch0)
Ref.
CH0
Information
Carry flag
U9.1.0
0: disable, 1: enable
BIT
Borrow flag
U9.1.1
0: disable, 1: enable
BIT
Current counter value
U9.2
-2,147,483,648 ~ 2,147,483,647
DINT
Error code
U9.4
Indicates error code
INT
8.7.2 Error code
Error
code
(Dec.)
Error contents Ref.
21
Pulse input type range setting error
22
CH1(3) RUN request while CH0(2) 2-phase RUN
* CH1(3) is not available when CH0(2) operate as 2-phase mode
25
Internal preset value exceeded counter range
Note
If more than two errors occur, the latest error code is saved and previous error code is removed.