Chapter 3 Installation and Wiring
XBC E-Type Main Unit 3-29 Ver. 1
Input Specifications
Input point 8 point, 1 COM
Insulation method Photo-coupler insulation
Rated input voltage DC24V
Rated input current 4mA (point 0-3: 7mA)
Operation voltage range DC20.4~28.8V (within ripple rate 5%)
On voltage / On current DC19V or higher / 3mA or higher
Off voltage / Off current DC6V or lower / 1mA or lower
Input resistance About 5.6kΩ (P00-P03: 2.7kΩ)
Response
time
Off → On
1/3/5/10/20/70/100ms (set by I/O parameter) default: 3ms
On → Off
Insulation
Voltage/Resistance
AC560Vrms / 3 cycle (altitude 2000m); 10MΩ or higher
Output Specifications
Rated load
voltage/current
DC24V 2A (resistive load) / AC220V 2A (COSΦ = 1), 5A/COM, 3 COM (Isolated)
Min. load voltage/current
Service life
Electrical
Rated load voltage / Current 100,000 times or more
AC200V / 1.5A, AC240V / 1A (COSΦ = 0.7) 100,000 times or more
AC200V / 1A, AC240V / 0.5A (COSΦ = 0.35) 100,000 times or more
DC24V / 1A, DC100V / 0.1A (L / R = 7
㎳