Chapter 4 CPU Specifications
XBC E-Type Main Unit 4-3 Ver. 1
Items
Specifications (“E” type)
Remark
XBC-DR10E XBC-DR14E XBC-DR20E XBC-DR30E
XBC-DN10E XBC-DN14E XBC-DN20E XBC-DN30E
XBC-DP10E XBC-DP14E XBC-DP20E XBC-DP30E
Internal consumption current
250mA 280mA 350mA 470mA
180mA 190mA 200mA 210mA
180mA 190mA 200mA 210mA
Weight
330g 340g 450g 465 g
313g 315g 418g 423g
313g 315g 418g 423g
Items
Specifications
“E” type
Built-in Function
Cnet I/F function
Dedicated protocol support
MODBUS protocol support
User defined protocol support
Select one port between RS-232C 1 port, RS-485 1 port by parameter
High-speed counter
Capacity
1 phase: 4 kHz 4 channel
2 phase: 2 kHz 2 channel
Counter
mode
4 different counter modes according to input pulse and addition/subtraction
method
1 phase pulse input: addition/subtraction counter
1 phase pulse input: addition/subtraction counter by B phase
2 phase pulse input: addition/subtraction counter
2 phase pulse input: addition/subtraction by rising pulse phase
differences (encoder)
Additional
function
Internal/External preset function
Latch counter function
Comparison output function
Revolution number per unit time function
Pulse catch
50
4 point (P0000 ~ P0003)
External interrupt
4 point: 50
(P0000 ~ P0003)
Input filter
Select among 1,3,5,10,20,70,100
(Adjustable)