Chapter 12 Troubleshooting MASTER-K
12-12
(Continued)
Error
Code
Error CPU state Message Cause
Corrective
Actions
0015h
FMM 2 I/F
error
Stop
FMM 2 I/F
ERROR
FMM 2 I/F Error
Contact the
service center.
0016h
FMM 3 I/F
error
Stop
FMM 3 I/F
ERROR
FMM 3 I/F Error
Contact the
service center.
0020h
Parameter
Error
Stop
PARAMETE
R ERROR
A written parameter has
changed, or checksum error
Correct the
content of the
parameter.
0021h
I/O
Parameter
Error
Stop
(continue)
I/O PARA
ERROR
When the power is applied or
RUN starts, I/O unit
reservation information
differs from the types of real
loaded I/O units.
Correct the
content of the
parameter, or
reallocate or
replace the I/O
unit.
0022h
Maximum
I/O Over
Stop
I/O PARA
ERROR
The point of the reserved I/O
information or real loaded I/O
units overruns the maximum
I/O point.
Correct the
content of the
parameter.
0023h
FMM 0
Parameter
Error
Stop
FMM 0
PARA
ERROR
FMM 0 Parameter Error
Correct the
parameter.
0024h
FMM 1
Parameter
Error
Stop
FMM 1
PARA
ERROR
FMM 1 Parameter Error
Correct the
parameter.
0025h
FMM 2
Parameter
Error
Stop
FMM 2
PARA
ERROR
FMM 2 Parameter Error
Correct the
parameter.
0026h
FMM 3
Parameter
Error
Stop
FMM 3
PARA
ERROR
FMM 3 Parameter Error
Correct the
parameter.
0030h
Operation
Error
Stop
OPERATION
ERROR
• A digit of other than 0 to 9
has met during BCD
conversion.
• An operand value is
outside the defined operand
range.
Correct the
content of the
error step.
0031h WDT Over
Continue
(stop)
WDT OVER
ERROR
Scan time has overrun the
watch dog time.
Check the
maximum scan
time of the
program and
modify the
program or insert
programs.
0032h
Error of
Program
Change
Stop
PGM
CHANGE
ERROR
An error has occurred at
program change during run.
(NO SBRT, JME and END
…)
Program
replaceme nt has
not been
completed during
run. (JMP ~ JME,
FOR ~ NEXT,
CALLx and
SBRTx …)
0033h
Program
Check
Error
Continue
CODE
CHECK
ERROR
An error has occurred while
checking a program.
Correct the error.