Chapter 12 Troubleshooting MASTER-K
12-13
(Continued)
Error
Code
Error CPU state Message Cause
Corrective
Actions
0040h
Code Check
Error
Stop
CODE
CHECK
ERROR
An instruction unreadable
by the CPU is included.
Correct the error
step.
0041h
Missing the
END
instruction in
the program.
Stop
MISS END
ERROR
The program does not
have the END instruction.
Insert the END
instruction at the
bottom of the
program.
0042h
Missing the
RET
instruction in
the program.
Stop
MISS RET
ERROR
The subroutine does not
has the RET instruction at
its bottom.
Insert the END
instruction at the
bottom of the
program.
0043h
Missing the
SBRT
instruction in
the
subroutine
program.
Stop
MISS SBRT
ERROR
The subroutine does not
has the SBRT instruction.
Insert the SBRT
instruction.
0044h
The JMP ~
JME
instruction
error
Stop
JMP(E)
ERROR
The JMP ~ JME instruction
error
Correct the JMP ~
JME instruction.
0045h
The FOR ~
NEXT
instruction
error
Stop
FOR~NEXT
ERROR
The FOR ~ NEXT
instruction error
Correct the FOR ~
NEXT instruction.
0046h
The MCS ~
MCSCLR
instruction
error
Stop
MCS~MCSC
LR ERROR
The MCS ~ MCSCLR
instruction error
Correct the MCS ~
MCSCLR
instruction.
0047h
The MPUSH
~ MPOP
instruction
error
Stop
MPUSH ~
MPOP
ERROR
The MPUSH ~ MPOP
instruction error
Correct the
MPUSH ~ MPOP
instruction
0048h
Dual coil
error
Stop
DUAL COIL
ERROR
Timer or counter has been
duplicated.
Correct timer,
counter.
0049h Syntax error Stop
SYNTAX
ERROR
Input condition error, or too
much use of LOAD or
AND(OR) LOAD.
Check and correct
the program.
0050h Battery error Continue
BATTERY
ERROR
Backup battery voltage
error
Replace the
battery under the
present condition.

Table of Contents