Use STP (Shielded Twisted Pair) cables to connect a remotely located motor with the
inverter. Do not use 3 core cables.
Make sure that the total cable length does not exceed 492 ft (150 m). For inverters < = 3.7
kW capacity, ensure that the total cable length does not exceed 165 ft (50 m).
Long cable runs can cause reduced motor torque in low frequency applications due to
voltage drop. Long cable runs also increase a circuits susceptibility to stray capacitance
and may trigger over-current protection devices or result in malfunction of equipment
connected to the inverter.
Voltage drop is calculated by using the following formula:
Voltage Drop (V) = [
3 X cable resistance (mΩ/m) X cable length (m) X current (A)] / 1000
Use cables with the largest possible cross-sectional area to ensure that voltage drop is
minimized over long cable runs. Lowering the carrier frequency and installing a micro surge
filter may also help to reduce voltage drop.
Distance
< 165 ft (50 m)
< 330 ft (100 m)
> 330 ft (100 m)
Allowed Carrier Frequency <15 kHz <5 kHz <2.5 kHz

Other manuals for LSIS SV-iS7 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS SV-iS7 series and is the answer not in the manual?

LSIS SV-iS7 series Specifications

General IconGeneral
BrandLSIS
ModelSV-iS7 series
CategoryInverter
LanguageEnglish

Related product manuals