Chapter 8 Dedicated Protocol Communication
8-13
(3) Response format (in case of PLC ACK response)
■ Write Response of Continuous Variable (PLC MMI)
Normal if it is 0, abnormal if not 0.
If Error State abnormal, the lower Byte is error code.
h0001: If Error State normal.
Header Instruction Data type
Reserved
1) Data type
Available data type is byte (%MB,%IB,%QB).
2) Number of data
It means the number of bytes (Hexadecimal).
(4) Response format (in case of PLC NAK response)
Format
.... h0059 h0014 h0000 hFFFF h21
1) Error code
Error code is attached the type of error in 1 byte of Hexadecimal code.
Refer to ‘Error Codes Table’ for more details.