Chapter 5 XG5000 Program
5-21
5.5 Connect and Download to Communication Module
5.5.1 Download/Upload
XG5000 can be used for downloading (writing) specified parameters or uploading (reading) the
parameters stored in the PLC.
(1) Write (download)
Connect with CPU of the basic base FEnet I/F module installed on whose parameters are
desired to write through [Online] -> [Connect] menu.
[Fig. 5.5.1] Connect menu
After connection is established, select [Online] -> [Write(standard settings, HS link, P2P)] to
display [Fig. 5.5.1] screen, where to specify standard settings items of the base and slot
positions FEnet I/F module to write (download) is installed on.
Notes
1) XG5000 can be programmed through RS-232C port or USB port of CPU module. Refer to CPU
Module’s connection diagram for detailed cable type.