Chapter 2 Product Specifications
2-1
Chapter 2 Product Specifications
2.1 General Specifications
General specifications of XGT series are as shown in Table 2.1.
No. Items Specification Reference
1
Ambient Temp.
0 ~ 55
°
C
2 Storage Temp. 25 ~ +70 °C
3 Ambient humidity 5 ~ 95%RH (Non-condensing)
4
Storage humidity
5 ~ 95%RH (Non-condensing)
5 Vibration Immunity
Occasional vibration
-
Frequency
Acceleration
Pulse width
Times
IEC61131-2
5
f
<
8.4Hz
3.5mm
10 times
each
direction (X,Y
and Z)
8.4
f
150Hz
9.8m/s
2
(1G)
Continuous vibration
Frequency
Acceleration
Pulse width
5
f
<
8.4Hz
1.75mm
8.4
f
150Hz
4.9m/s
2
(0.5G)
6 Shocks Immunity
Peak acceleration : 147 m/s
2
(15G)
Duration : 11ms
Pulse wave type : Half-sine (3 times each direction per each axis)
IEC61131-2
7 Noise Immunity
Square wave
impulse noise
AC : ±1,500V
DC : ±900V
LSIS internal
test spec.
Electrostatic
discharge
Voltage: 4kV (Contact discharge)
IEC61131-2
IEC61000-4-2
Radiated
electromagnetic
field noise
80 ~ 1000 MHz, 10V/m
IEC61131-2,
IEC61000-4-3
Fast transient
/Burst noise
Classific
ation
Power
supply
Digital/Analog Input/Output,
Communication Interface
IEC61131-2
IEC61000-4-4
Voltage
2kV
1kV
8
Operation
ambience
Free from corrosive gases and excessive dust
9 Altitude Less than 2,000m
10 Pollution degree Less than 2
11 Cooling method Air-cooling
1) IEC(International Electro technical Commission.
: An international nongovernmental organization which promotes internationally cooperated standardization in
electric/electronic fields, publishes international standards and manages applicable estimation system related
with.
2) Pollution level
: An index indicating pollution level of the operating environment which decides insulation performance of the
devices. Generally, Pollution level 2 indicates the state that only non-conductive pollution occurs generally.
However, this state contains temporary conduction due to dew produced.