Chapter 8 Dedicated Communication
8-14
8.2.5 Status Read Request (MMI -> PLC)
(1) Introduction
This service allows the user to use information and status of PLC through communication.
(2) Computer Request format
(3) Response format (ACK Response from PLC)
Normal if it is 0, abnormal if not 0.
(4) Data structure of XGT status
Item
Size
Description
Slot Info 4 0
Slot information
Bit00~Bit03: Local’s slot information remotely connected with other station.
Bit04~Bit07: Local’s base information remotely connected with other station.
Bit08~Bit11: Other station’s slot information remotely connected.
Bit12~Bit15: Other station’s base information remotely connected.
Bit16~Bit19: Slot information this module is installed on.
Bit20~Bit23: Base information this module is installed on.
XG5000 connection status : Flag
PLC mode and operation status : Flag
System error (serious) : Flag
* Refer to Description of flags below for more details on respective items.