Chapter 10 Troubleshooting
10-1
Chapter 10 Troubleshooting
This chapter is to describe various errors that may occur in system operation, their causes and actions
to take against. Follow the procedures below to check for errors and error details in XGT FEnet I/F
module. And take suitable actions against the abnormal module states surely through the troubleshooting
in proper procedures. Discretionary repair or disassembly is not allowed. Because A/S does not have
it, please be careful based on A/S rule.
10.1 Check through Communication Module LED
The status of the communication module can be checked through LED display.
10.1.1 Abnormal operation display of XGL-EFMT/EFMF
The operation status can be checked through LED in front of Ethernet module.
< LED of XGL-EFMT >
[Fig.10.1.1] LED structure of XGL-EFMT/EFMF module
LED
Error Action
RUN
Turned off after
FEnet powered on
1) Ethernet communication module incorrectly installed
- check DC 5V power supply of power module.
- check the communication module if correctly installed on
the base.
2) Check if communication module is correctly perceive
d with
XG5000.
I/F
LED on or off during
normal communication
1) Check the operation state of CPU module.
2) Check the communication module if correctly installed on the
base.
3) Check if module information is correctly perceived with
XG5000 software.
P2P
Turned off during
P2P command service
1) Check if the basic parameter is downloaded correctly.
2) Check if the function block/command is edited correctly.
3) Check if the media is connected correctly.
4) Check if Link Enableis enabled.
XGL-EFMT
RUN
HS PC I/F
P2P TX
PADT
ERR RX
10/100