Safety Instructions for design process 
 
 
 
 
 
 
 
 
 
 
 
1. Please install a protection circuit on the exterior of PLC so that the 
whole system may operate safely regardless  of failures from 
external power or PLC. Any abnormal output or operation from PLC 
may cause serious problems to safety in whole system.   
(1) Install protection units on the exterior of PLC like an interlock circuit 
that deals  with  opposite operations such as 
protection circuit, and forward/reverse rotation or install an interlock 
circuit that deals with high/low limit under its position controls. 
(2) If any system error (watch-dog timer error, module installation error, 
etc.) is detected during CPU operation in PLC, all output signals are 
designed to be turned off and stopped for safety. However, there 
are cases when output signals remain active due to device failures 
in Relay and  TR  which  can’t be detected
recommended  to install an addition circuit to monitor  the output 
status for  those  critical outputs which may cause  significant 
problems.   
2. Never  overload more than rated current of output module nor 
allow to have a short circuit. Over current for a long period time may 
cause a fire . 
3. Never let the external power of the output circuit to be on earlier   
than PLC power, which may cause accidents from abnormal output or 
operation. 
4. 
Please install interlock circuits in the sequence program for safe 
operations in the system when exchange data with PLC or modify 
operation modes using a
computer or other external equipments 
Read specific instructions thoroughly when conducting control