Chapter 5 XG5000 Program 
 
5-9 
 1) TCP/IP setting   
High-speed 
link station No. 
Specify station No. for High-speed link communication between LSIS PLCs’ FEnet 
I/F modules, which shall not be duplicated identically to the correspondent 
Media 
Select media to use. 
 AUTO (electric) : automatically detects the module presently installed. 
 10M/HALF : 10MBps Half Duplex electric 
 10M/FULL : 10MBps Full Duplex electric 
 100M/HALF : 100MBps Half Duplex electric 
 100M/FULL : 10MBps Full Duplex electric 
 FX/100M/HALF  : 100MBps Half Duplex optical 
 FX/100M/FULL  : 100MBps Full Duplex optical 
Specify the IP Address of the applicable FEnet I/F module. 
Subnet mask
 
Value necessary to check if destination station 
is on the same network of the 
applicable station.
 
Gateway 
 
IP address of Gateway  or  R
outer to transmit/receive data through the public 
network or a network different from the network where  the 
applicable FEnet 
module is included.
 
Specify the IP address of domain name server.
 
Check DHCP option when not fixed but dynamic IP is to be used (ADSL). 
Using when send frame received at one port to another port. 
Reception 
wating time
 
If there is no request during the specified time from the host PC or MMI connected 
for dedicated communication,  it will end the dedicate
regardless of normal ending procedures supposing that the higher level 
with error. This time is used in dedicated service to reset the channel 
error occurs on the destination station or the cable is disconnected.
 
Number of 
dedicated 
Max. number of TCP dedicated services accessible at a time. (1~16)
 
2) Driver (server) setting 
Set when operated as dedicated communication server (slave) 
Set when operated as Modbus server driver (slave) 
Access allowed to applicable module of IP address registered in host table 
(unregistered client(IP address) is prohibited from connection when enabled)