Chapter 5 XG5000 Program 
 
5-14 
 (2) Setting communication module 
  
 
[fig.5.3.3] Setting of communication module and communication period 
 
 
Classification
 
Description
 
Communication 
module settings
 
Module type
 
Select FEnet.
 
Base No.
 
Select Base No. the module is installed on. 
Slot No.  Select Slot No. the module is installed on. 
Communication 
period settings 
Period type 
Set the data transmission period. 
(available range is 20ms~10sec) 
Output data setup 
in case of 
emergency 
Latch 
Maintain and send the latest data received from CPU. 
It is seen that it is cleared if CPU sends data as 0 
even though latch is set. Make sure to check the 
emergency output data setting of CPU.   
Clear 
It sends by setting received High-speed Link data as 0 
in ignoring data from CPU. If emergency data is set as 
‘clear’ in emergency output data setting of XG5000 
High-
speed Link module setting even though 
emergency output data setting of device area of High-
speed Link sending part is set as latch in CPU, the 
data set as 0 is sent. Make sure to set it after 
checking desired operation.