Using the menus
Setup menus (quick setup)
Object
Instance
Setup menu
Options Function
MSV127
Preset Select application
MSV64
CFGunit Units configuration Metric
Imper
Sets the system for using metric units (Degree C)
Sets the system for using imperial units (Degree F)
MSV1
CFGSens Remote thermistor type Type 3
Type 2
Sets remote thermistor types to 10K
-3 (10K type 3)
Sets remote thermistor types to 10K
-2 (10K type 2)
AV50
RT_Cal Room temperature calib - 3.00 (C/F)
+ 3.00 (C/F)
Allows calibration of the room sensor used for the main temperature control loop of the thermostat. Default is (0.00 C/F)