Please note that objects tagged as:
Cfg: represent configuration properties of the device that are typically only set once during commissioning and start-up
User: represent properties or objects that are typically manipulated by users of the controller
Status: represent objects or properties that are ‘’typically’’ meant to be displayed on graphics for various required visualization
Cmd: represent objects that can be controlled directly by other BACnet external process
Multi-State Values
Object
Instance
RTU
Object name
Description
Tags
Default value State texts
MSV54
AI_SRH Select supply humidity input Cfg None None
AI-1
AI-2
AI-3
AI-4
External
MSV55
AIC_SRH Set supply humidity input signal Cfg 0-10V 0-10V
2-10V
MSV57
OAH_Loc Outside humidity physical input loc. Cfg None None
AI-1
AI-2
AI-3
AI-4
External
Intern
MSV58
MAT_OCC Mixed air temperature sensor loc. Cfg None None
AI-1
AI-2
AI-3
AI-4
External