Cfg: represent configuration properties of the device that are typically only set once during commissioning and start-up
User: represent properties or objects that are typically manipulated by users of the controller
Status: represent objects or properties that are ‘’typically’’ meant to be displayed on graphics for various required visualization
Cmd: represent objects that can be controlled directly by other BACnet external process
www.lynxspring.com
Multi-State Values
Object
Instance
RTU
Object name
Tags Default value State texts
MSV70
PB
Description
CFG Heating/cooling proportional band Cfg 5F 2.2C 3F 1.2C
4F 1.7C
5F 2.2C
6F 2.8C
7F 3.3C
8F 3.5C
9F 5.0C
10F 5.6C
MSV75
KeyLock SCFG Keypad lock level Cfg None None
Fan
Mode
FanMode
All