When measuring is completed, impedance of
L- PE PFC (lf) value appears on the screen
Press TEST button if re-test is necessary.
When symbol from , ,
appears lower left corner, and if the voltage
260V, the measurement will not take
5.2.3-Using the Hi Amp LOOP Measurement to be
selected where the circuit is NOT protected the
inclusion of an RCD
Turn the rotary switch to the LOOP / PFC position
Press F2 button to change from No Trip to Hi Amp
Connect the test leads as shown in the
-
and
exceeds place
by
If voltage of the L- PE on the lower left appears, the
unit is ready to TEST
Press the TEST button when ready
-
1-
-
-8
4-
5-
1
1
1
1
1
-
-
-
-
-
18
Multifunction Tester User Manual