EC65 SELF-CONTAINED WATER-COOLED — STANDARD CUBE (Continued)
Operating Pressures
Condenser Water
Consumption
32 Air Temperature Around Ice Machine
Water Temperature °C
15 21 32
Gal/24 Hours 689 1057 9488
Water Temperature
Entering Condenser °C
Freeze Cycle Harvest Cycle
Discharge Pressure Suction Pressure Discharge Pressure Suction Pressure
Set water regulating valve to 15.9 bar 5 minutes into freeze cycle. All pressures are in bar. Suction
pressure drops gradually throughout the freeze cycle.
10 15.86-15.51 4.55-1.93 6.89-10.00 5.52-6.89
20 15.86-15.51 4.83-1.93 7.58-10.68 6.21-7.93
25 15.86-15.51 4.83-1.93 7.58-10.68 6.21-7.93
32 16.20-15.86 4.83-2.00 7.93-11.03 6.89-8.27
43 17.24-16.20 5.17-2.14 8.27-12.41 7.58-8.96