Part Number 80-1479-3 10/10 37
HOT GAS VALVE WON’T ENERGIZE
No Timer Models
1. Verify the evaporator temperature is below setpoint,
then refer to evaporator thermostat check
procedure to verify the evaporator thermostat is
operating correctly.
2. Line voltage at hot gas valve? (Wires 6& 7)
Yes - Replace hot gas valve coil.
No - Refer to evaporator thermostat diagnostics.
(22)
HOT GAS
SOLENOID
WATER INLET
SOLENOID
EVAP THERMOSTAT
(21)
(7)
(10)
(6)
C
H
L
(3)
1