Part Number 80-1479-3 10/10 43
WATER INLET VALVE WON’T ENERGIZE
Mechanical Timer
The hot gas valve and water inlet valve energize
together in the harvest cycle. If the hot gas valve
energizes verify #1 and then go right to #4.
1. Water supplied to the ice machine?
2. Toggle switch terminals 2 & 1 closed?
(wires #64 & #3)
3. Timer micro switch closed (relay 1)?
(wires #3 & #6)?
4. Water inlet valve coil winding closed?