Model: LC5296-AT /LC5248E-AT/LC5296V-AT masibus
Doc. Ref. no. : - m61C/om/301
Issue no. 13
User’s Manual Page 22 of 44
6.6 CONFIGURATION MODE
Adjust Cycle Time
For, SSR o/p: (1 – 60 sec)
Relay o/p: (10 – 300 sec)
Set Output Direction dir/rev
0 : REV (REVERSE)
1 : DIR (Direct)
Control Type(COP)
is P or PI or PID
Adjust Manual Reset Value
It is used to shift P Band for critical Controlling
situations.
-50% to 50% of PB
EX. If PB = 50, SP = 100, O.DIR = REV
MR = 0MR = 25
Control Type(COP)
is P or PI or PID
Adjust Sampling Rate
Its acts like Derivative Factor. It is used to decrease
effect of D term in PID output for some critical
operating condition
0.01 to 1.00
Set Sampling Period. 200 /500 /1
0 : 200 ms
1 : 500 ms
2 : 1 sec
n o n e /m i n . r /hr.r
0:none
1:min.r
2:hr.r
0.1 to 999.9 Degree per minutes or hour
s.hod/s.rst
0:s.hod
1:s.rst
CONFIG URAT IO N PARAME TE RS
Setting Name & Description
Set PV Input Type
tC e/tC j /tC K /tC t /tC b /tC r /tC s
/rtd.1 /rtd/0-5v /1-5v / 0-10