EasyManuals Logo

Masibus LC5296-AT User Manual

Masibus LC5296-AT
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background imageLoading...
Page #41 background image
Model: LC5296-AT /LC5248E-AT/LC5296V-AT masibus
Doc. Ref. no. : - m61C/om/301
Issue no. 13
User’s Manual Page 41 of 44
11.2 ON-OFF LOGIC
Relay type
PV
Relay
LED
Hi-On
PV > SP
On
On
PV < SP
Off
Off
Open sensor
Up scale
On
On
Down scale
Off
Off
Low-On
PV > SP
Off
Off
PV < SP
On
On
Open sensor
Up scale
Off
Off
Down scale
On
On
11.3 Retransmission Output Table for OPEN /OVER /UNDER Condition
RETRASMISSION
VARIABLE
SCALE
ACTION
OPEN
OVER
UNDER
4-20mA
PV
UP
DIR
20.8
20.8
3.2
PV
DOWN
REV
3.2
3.2
20.8
PV
UP
REV
20.8
3.2
20.8
PV
DOWN
DIR
3.2
20.8
3.2
1-5V
PV
UP
DIR
5.2V
5.2V
0.8V
PV
DOWN
REV
0.8V
0.8V
5.2V
PV
UP
REV
5.2V
0.8V
5.2V
PV
DOWN
DIR
0.8V
5.2V
0.8V
NOTE: -
1. OPEN/UNDER/OVER condition is applicable to all input types except 0-5v /
0-20mA.
11.4 Linear Output Table for OPEN/OVER/ UNDER Condition
CONTROL OP
Process
Scale
Output
Direction
(O.DIR)
DISPLAY INDICATION
OPEN
OVER
UNDER
4-20mamp
UP
DIR
20.0
20.0
4.0
Current
DOWN
REV
4.0
4.0
20.0
UP
REV
20.0
4.0
20.0
DOWN
DIR
4.0
20.0
4.0
SSR
UP
DIR
ON
ON
OFF
Pulse Output

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Masibus LC5296-AT and is the answer not in the manual?

Masibus LC5296-AT Specifications

General IconGeneral
BrandMasibus
ModelLC5296-AT
CategoryController
LanguageEnglish

Related product manuals