EasyManua.ls Logo

McQuay TSC User Manual

McQuay TSC
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #94 background imageLoading...
Page #94 background image
94 OM Centrif Micro ΙΙ-5
Sequence of Operation
Unit Operation
The following sequence of events describes a typical WDC start and second compressor staging
process. All the contingency features of the code are not necessarily included. The purpose of this
document is to provide the operator with some insight into how the centrifugal chiller distributed
control process works to start and stage compressors.
The code was laid out to control four chillers with four compressors on each chiller. The polling
routine described below searches for all possible compressors (16 total), the code works the same
rather in a standalone WSC, or in a Dual (2 chiller) WDC setup. The Max Comp On setpoint is
used to limit the number of compressors that can run at one time (not the number being polled).
Chiller Starting
1. When the Unit state is switched to Auto, the compressors on a dual, or multi-compressor setup,
poll each other (1 to 2 minutes) to determine which will be NEXT_ON. The outcome of the
NEXT_ON search is determined by the Staging Sequence selected by the operator. Only one
compressor at a time can be selected to be NEXT_ON, and only compressors without active
alarms. The NEXT_ON status is indicated by lighting the right arrow button on that
compressor's controller keypad. If the NEXT_ON compressor has Start-to-Start or Stop-to-
Start timers running, the chiller will wait for them to clear.
2. When the Unit controller receives the NEXT_ON flag from one of its compressors, it will
start its Evap Pump (Evap Start State) and wait for the Recirculation time, at a minimum, then
it will wait "till the end of time" for the flow switch to close. When flow is confirmed, the
Evap State will switch to Run.
3. Approximately one min after NEXT_ON is set in the compressor, the compressor will look at
the Evap LWT to determine if Start-Delta-T has been exceeded. If so the Stage-Up-Now flag
is set, and if Evap State equals Run, the compressor start sequence will begin [Comp Start (oil
pump) state].
4. When the required net oil pressure is achieved, the compressor will transition to PreLube state
and when the Vanes_Closed switch is made (compressor cleared to start) the Unit controller
will start the Condenser Pump.
If the Vanes_Closed switch is not made within the Prelube time plus 30 seconds, a Vanes-
Open-No-Start alarm is declared.
If condenser flow is not established within a time period after the vanes closed signal, a
Condenser Flow alarm is declared. The time period is equal to the Prelube time plus 30
seconds. Note: It is possible for the Prelube state to successfully run for twice the Prelube
time plus 60 seconds, and not create an alarm.
While running, if flow is lost and a secondary pump is available, the primary pump output will
be turned off and the secondary pump output turned on. The time required is one-half of the
flow proof set point value.
5. In order to transition from Prelube to Compressor run state the following flags must be set:
Unit_State_Auto, Evap_State_Run, Cond_State_Run, Vanes_Closed, and Prelube timer
expired. Given this the lead compressor will start.
Compressor Staging
1. If the Normal (default) Staging Sequence on a WDC chiller is selected, and a compressor (the
lead) has just started, the lag compressors polling routine will declare it as the NEXT_ON
compressor.

Questions and Answers:

McQuay TSC Specifications

General IconGeneral
BrandMcQuay
ModelTSC
CategoryController
LanguageEnglish

Summary

Features of the Control Panel

General Description

Component Description

Unit Controller

Compressor Controller

Field Wiring Diagram

Dual/Multi-Chiller Operation

Multiple Chiller Setup

Describes interconnecting up to four chillers via pLAN.

pLAN Setup

Details RS485 wiring and configuration for multi-chiller setup.

Communication Wiring

MicroTech II Operator Interface Touch Screen (OITS) Settings

Maximum Compressors ON

Sets the maximum number of compressors allowed to run.

Sequence and Staging

Defines the sequence in which compressors will start and stage.

Nominal Capacity

Sets the compressor design tons.

Operating Sequence

Operator Interface Touch Screen

SET Screens

Editing Setpoints

Details the process for accessing and changing setpoints.

Typical SETPOINT Screen

Procedure for Changing a Setpoint

Details the step-by-step process for modifying setpoint values.

Explanation of Setpoints

TIMERS

For setting timers like start-to-start, prelube, and postlube.

ALARMS

For setting limit and shutdown alarms.

VALVE

For tower bypass valve operation parameters.

TOWER

For cooling tower fan control and parameters.

MOTOR

For motor-related setpoints like amp limits.

MODES

For selecting operating modes and staging.

WATER

For leaving water temp, delta-T, and resets.

STARTER SETPOINTS

Optional Starter Setpoint Screen

Displays and allows setting of starter-specific parameters.

TIMERS Setpoint

TIMERS Setpoint Screen

Allows adjustment of various timing parameters for operation.

ALARMS Setpoint

ALARMS Setpoint Screen

Allows configuration of alarm limits and shutdown conditions.

Cooling Tower Bypass Valve Settings

Tower Bypass Valve Setpoint Screen

Configures parameters for the cooling tower bypass valve operation.

Cooling TOWER Fan Settings

Cooling TOWER Fan Setpoint Screen

Sets parameters for cooling tower fan staging based on temperature or lift.

Explaination of Tower Control Settings

Tower Fan Staging Only (NONE)

Configuration for tower fan staging without bypass valve or VFD control.

Tower Fan Staging With Bypass Valve Controlling Minimum EWT (VALVE SP)

TOWER SETPOINT Screen

Setpoints for tower fan staging with bypass valve controlling minimum EWT.

VALVE SETPOINT Screen

Setpoints for valve control in this mode.

Tower Staging with Bypass Valve Controlled by Fan Stage (VALVE STAGE)

Fan VFD, No Bypass Valve (VFD STAGE)

MOTOR Setpoint Screen

MOTOR Setpoint Screen

Configures motor parameters like FLA, speed, and limits.

MODES Setpoints

MODES Setpoint Screen

Selects operating modes, compressor staging, and control sources.

WATER Setpoints

WATER Setpoint Screen

Configures water temperature setpoints and reset parameters.

SERVICE Screen

Service Screen

Provides access to unit status, versions, and maintenance functions.

ACTIVE ALARM Screen

Active Alarms Screen

Displays current active alarms with date, time, and cause.

Fault Alarms

Problem Alarms

Warning Alarms

Set Screens

Unit and Compressor Setpoints

Configuration of unit and compressor parameters like mode, staging, and limits.

Alarm and Tower Setpoints

Configuration of alarm limits and cooling tower control settings.

View ALARM Screens

Active Alarm Screen

Shows currently active, uncleared alarms.

Editing Setpoints

Unit Controller Setpoints

Table 23, Unit Setpoints

Comprehensive list of unit controller setpoints, defaults, and ranges.

EXV Control Parameters

Set Compressor Setpoints

Staging Parameters

Set Alarm Setpoints

Set Tower Setpoints

Alarms

Compressor Controller Setpoints

Table 24, Compressor Setpoints

Compressor Setpoints

Low Voltage Starters, 200 – 600 Volts

Solid State Starter Overview

Operation

Restoring Factory Parameter Settings

Faults and Alarms

Alarm Definitions

Troubleshooting

Fault Code

Preventive Maintenance

Medium/High Voltage Starters, 2300V – 7.2KV

View Parameters

Set Parameters

Menu Structure

Quick Start

Max. Curr. (maximum current)

Ramp Time

Overload

Phase Order

Fault/Log Codes

Sequence of Operation

Determining Full Load Status

Full Load Determination

Defines conditions for a compressor reaching full load status.

Operating the Chiller Control System

Change Setpoints

Component Failure

Standby Power

Maintenance Schedule

I. Unit

Unit-specific maintenance tasks including logs and leak tests.

II. Compressor

Compressor maintenance tasks, including motor and lubrication.

III. Controls

Maintenance for operating and protective control systems.

Maintenance Schedule, Cont.

IV. Condenser

Condenser maintenance including tube cleaning and temp approach.

V. Evaporator

Evaporator maintenance including tube cleaning and temp approach.

VII. Starter(s)

Starter inspection, overload verification, and electrical connection checks.

Related product manuals