115
Tens place: Main digital frequency stop control
0: The set frequency will be maintained upon stop
When the drive is stop, the set value of the main digital frequency is the final modified value.
1: The set frequency will restore to P02.05 upon stop
When the drive is stop, the set value of the main digital frequency will restore to P02.05 automatically.
Hundreds place: Auxiliary digital frequency storage control
0: The auxiliary frequency will be saved upon power down
The auxiliary frequency will be saved into P02.08 upon power down
1: The auxiliary frequency will not be saved upon power down
Not be saved upon power down.
Thousands place: Auxiliary digital frequency stop control
0: The auxiliary frequency will be maintained upon stop
The auxiliary frequency is maintained upon stop.
1: The set frequency is reset upon stop
The auxiliary frequency is reset upon stop.
0: No auxiliary reference
The set frequency is composed of the main set frequency only and the auxiliary set frequency is 0 by
default
1: Digital reference 1, adjusting with the
∧ & ∨ keys on the operation panel
The initial value of the auxiliary frequency is P02.08, which can be adjusted with the
∧ & ∨
keys on
the operation panel.
2: Digital reference 2, adjusting with terminal UP/DOWN
The initial value of the auxiliary frequency is P02.08, which can be adjusted with the terminal UP/DOWN.
For the setting of terminal UP/DOWN, please refer to the function codes of Group P09.
3: Digital reference 3, serial port communication reference
The auxiliary frequency is set based on the serial port reference and its initial value is the value of P02.08.
The value of the auxiliary set frequency is changed through the serial port frequency setting command.
4: AI analog reference
The auxiliary frequency is set based on the AI terminal (AI1 and AI2) reference.
5: Terminal pulse (PULSE) reference
The auxiliary frequency is determined by the terminal pulse frequency and can be input by X6, please
refer to the definition in the function codes of Group P09 for details.
6: Process closed loop output
The process closed loop output is used as the auxiliary reference.
7: Field bus card reference
Set the reference via the Field bus card.
Auxiliary reference frequency source selection
0~7
0
P02.07