164 
 
0: Operate automatically   
Internal temperature detection program will be automatically started during the drive operation to 
determine the operation of the fan according to the module temperature. If the fan is running before the 
drive stop, the fan will run for another 3 minutes after the drive shuts down, and then the internal 
temperature detection program will be started. 
 
1: The fan keeps running when the power is on. 
The fan keeps running after the drive is powered up.   
2: Fun operates based on command 
When the drive will operate normally upon receiving the running command, the fan will also operate. 
When the drive stops running, so does the fan.   
 
 
 
6.11   Multi-stage reference and simple PLC parameters (Group 
P13) 
 
0: Multi-stage frequency reference   
As a frequency mode, it is applied to multi-speed operation mode and simple PLC operation mode.   
1: Multi-stage closed loop reference 
As a voltage reference, it is applied to the process PID operation mode.   
 
 
 
 
 
 
 
 
 
 
 
 
 
Reserved 0
P12.15~P12.27 
Multi-sta
e reference 13 -100.0~100.0%
90.0%
P13.13 
Multi-sta
e reference 12 -100.0~100.0%
80.0%
P13.12 
Multi-sta
e reference 11 -100.0~100.0%
60.0%
P13.11 
Multi-sta
e reference 10 -100.0~100.0%
40.0%
P13.10 
Multi-sta
e reference 9 -100.0~100.0%
20.0%
P13.09 
Multi-sta
e reference 8 -100.0~100.0%
10.0%
P13.08 
Multi-sta
e reference 6 -100.0~100.0%
90.0%
P13.06 
Multi-sta
e reference 5 -100.0~100.0%
80.0%
P13.05 
Multi-sta
e reference 4 -100.0~100.0%
60.0%
P13.04 
Multi-sta
e reference 3 -100.0~100.0%
40.0%
P13.03 
Multi-sta
e reference 2 -100.0~100.0%
20.0%
P13.02 
Multi-sta
e reference 1 -100.0~100.0%
10.0%
P13.01 
Multi-sta
e reference 
ro
ert
 settin
0~1 
0
P13.00 
Coolin
 fan control 0~2
2
P12.14 
Multi-sta
e reference 7 -100.0~100.0%
100.0%
P13.07