142
Set the logic state of X4~X1 as 0000, the corresponding hexadecimal value as 0, and then the LED will
display 0 at the unit place. Set the logic state of X6~X5 as 11, the corresponding hexadecimal value as 3,
and then the LED will display 3 at the tens place.
This function code is used to set the enabled state of the host device virtual input terminal. For the
detailed setting method, please refer to the description of P09.15.
0: Common open collector output
1: High-speed pulse output
Y2 and the relay terminal can be defined as the multi-functional digital output; in addition, Y1 can also be
used as the high-speed pulse output (0~50kHz) terminal. When Y1 terminal is used as the high-speed
pulse output terminal, please refer to relevant functions of P09.29.
Table of function definition of the multi-functional digital output:
Table 6-12 Function definition of the multi-functional digital output
Item Function Item Function
0 Drive in running state signal (RUN) 1 Frequency arrival signal (FAR)
2 Speed non-zero signal 3
Frequency level detection signal
(FDT1)
4
Frequency level detection signal
(FDT2)
5 Overload detection signal (OL)
6 Lockout for undervoltage (LU) 7 External fault stop (EXT)
8 Frequency upper limit (FHL) 9 Frequency lower limit (FLL)
10 Drive running at zero-speed 11
Simple PLC stage running
completion indication
12 PLC cycle completion indication 13 Reserved
14 Reserved 15 Drive ready for running (RDY)
16 Drive fault 17 Host device switch signal
18~33 Reserved 34 Drive FWD/REV indication
35 Motor 1 and 2 indication 36 Bus card ON/OFF signal
37~42 Reserved 43 PID feedback loss
44 PID feedback exceeding limit
0: Drive in running state signal (RUN)
When the drive is running, the relevant indication signal is output.
1: Frequency arrival signal (FAR)
Refer to the function description of P09.24.
2: Speed non-zero signal
Output selection of Y1
0~1
0
P09.17
Relay RO1 output function selection
0~44
15
P09.20
Open collector output terminal Y2
0~44
1
P09.19
Open collector output terminal Y1
0~44
0
P09.18
Virtual input terminal setting
00
3FH
00
P09.16