151
P10.02~P10.03 defines the channel filtering time constant for the filtering of the input signal. The longer
the filtering time is, the stronger the immunity becomes, but the slower the response will become. The
shorter the filtering time is, the faster the response becomes, but the weaker the immunity will become.
Fig.6-38 Analog and pulse curve selection
P10.05 is used for selecting the analog and pulse curve.
Reserved 0P10.04
Actual value corresponds to the inflection point 1 of the curve 1
0.0~300.0%
(
0.0%
)
P10.19
Inflection
p
oint 1 of the curve 1 reference P10.20~P10.16
(
0.0%
)
P10.18
Actual value corresponds to the inflection point 2 of the curve 1
0.0~300.0%
(
100.0%
)
P10.17
Inflection
p
oint 2 of the curve 1 reference P10.18~P10.14
(
100.0%
)
P10.16
Actual value corresponding to the maximum reference of curve 1
0.0~300.0%
(
100.0%
)
P10.15
Maximum reference of curve 1 P10.16~100.0%
(
100.0%
)
P10.14
Actual value corresponding to the minimum reference of line 2
0.0~300.0%
(
0.0%
)
P10.13
Minimum reference of line 2 0.0~P10.10
(
0.0%
)
P10.12
Actual value corresponding to the maximum reference of line 2
0.0~300.0%
(
100.0%
)
P10.11
Maximum reference of line 2 P10.12~100.0%
(
100.0%
)
P10.10
Actual value corresponding to the minimum reference of line 1
0.0~300.0%
(
0.0%
)
P10.09
Minimum reference of line 1 0.0%~P10.06
(
0.0%
)
P10.08
Actual value corresponding to the maximum reference of line 1
0.0~300.0%
(
100.0%
)
P10.07
Maximum reference of line 1 P10.08~100.0%
(
100.0%
)
P10.06
Analo
g
curve selection 0~2022H
(
0010H
)
P10.05
AI2 filterin
g
time 0.000~10.000s
(
0.010s
)
P10.03
AI1 filterin
g
time 0.000~10.000s
(
0.010s
)
P10.02