192
Fault
code
Fault type Possible fault cause Solutions
The power-up buffer resistance is
damaged.
Replace the buffer resistance, seek for service
support
The control circuit is damaged. Seek for service support
Input phase loss Check the input R.S.T. wiring
Er.CUr
Current detection
circuit abnormal
The wirings or the plug-in units of the
control board loosens.
Check them and rewiring
The auxiliary power supply is
damaged.
Seek for service support
The Hall device is damaged. Seek for service support
The amplifying circuit is abnormal. Seek for service support
The AI analog input voltage is too high.
Reduce the AI analog input voltage to less than
12V
Er.CPU
System
interference
Severely interfered
Reset by pressing STOP/RESET key or install a
power filter to the input side of the power supply
DSP read/write error of the main
control panel
Reset by pressing the STOP/RESET key, seek for
service support
Er.FbL
Closed loop
feedback loss
The parameters for feedback loss are
set improperly.
Modify the P14.26 setting
Feedback wire-break Rewiring
The reference of closed loop feedback
value is too low.
See the P14.01 setting and increase the feedback
reference
Er. EGL
External reference
command lost
During the frequency main reference
or the torque command selection
analog current reference, the analog
reference signal is disconnected or too
low (less than 2mA).
Check the wiring or adjust the input type of the
reference signal
Er.CoP
Operation panel
parameter copying
error
The operation panel parameters are
incomplete or the operation panel
version is inconsistent with main
control panel version.
Refresh the operation panel data and version, use
P00.06=1 for uploading the parameters first and
then use P00.06=2 or 3 for downloading.
The operation panel EEPROM is
damaged.
Seek for service support
Er.TUn Poor auto-tuning
The nameplate parameters of the
motor are incorrect.
Set the parameters properly according to the
motor nameplate