P00.03
Parameter
protection
setting
Parameter
protection
setting
0: All the data can be changed;
1: Only the main set frequency (digital
setting P02.05) and this function code
can be changed
2: Only this function code can be
changed
1 0
P00.04
Selection of
key
functions
Selection of
key functions
Unit place: Manufacturer
commissioning
Tens place: Function selection of the
STOP/RESET key
0: The STOP key is valid only in the
panel control mode
1: The STOP key is valid in all control
modes
Note: The RESET key is valid in any
control mode
Hundreds place: Function selection of
M key
0: No function
1: JOG
2: FWD/REV
3: Command channel switching 1
(valid only in stop status)
4: Command channel switching 2
(valid both in stop & running status)
5: Panel locking function
6: Emergency stop function
7: Coast to stop function
Thousands place: Panel locking
function
0: Lock all the keys
1: Lock all the keys except the STOP
key
2: Lock all the keys except the >> key
3: Lock all the keys except the RUN &
STOP key
1 0100 × ×
P00.05
Parameter
initialization
Parameter
initialization
0: Parameter changing status
1: Clear fault memory information
2: Restore to
leave-factory value
3: Restore the quick start function
group only
1 0 × ×
P00.06
Parameter
copy
Parameter
copy
0: Disabled
1: Uploading parameter
2: Downloading parameters
3: Downloading parameters (except
the motor parameters)
Note: The drive parameters will not be
uploaded/downloaded
1 0 × ×