65 
P00.03 
Parameter 
protection 
setting 
Parameter 
protection 
setting 
0: All the data can be changed; 
1: Only the main set frequency (digital 
setting P02.05) and this function code 
can be changed 
2: Only this function code can be 
changed 
1 0 √ √  ○ 
P00.04 
Selection of 
key 
functions 
Selection of 
key functions
Unit place: Manufacturer 
commissioning 
Tens place: Function selection of the 
STOP/RESET key 
0: The STOP key is valid only in the 
panel control mode 
1: The STOP key is valid in all control 
modes 
Note: The RESET key is valid in any 
control mode 
Hundreds place: Function selection of 
M key 
0: No function 
1: JOG 
2: FWD/REV 
3: Command channel switching 1 
(valid only in stop status) 
4: Command channel switching 2 
(valid both in stop & running status) 
5: Panel locking function 
6: Emergency stop function 
7: Coast to stop function 
Thousands place: Panel locking 
function 
0: Lock all the keys 
1: Lock all the keys except the STOP 
key 
2: Lock all the keys except the >> key 
3: Lock all the keys except the RUN & 
STOP key 
1 0100 × √ × 
P00.05 
Parameter 
initialization 
Parameter 
initialization 
0: Parameter changing status 
1: Clear fault memory information 
2: Restore to
 leave-factory value 
3: Restore the quick start function 
group only 
1 0 × √ × 
P00.06 
Parameter 
copy 
Parameter 
copy 
0: Disabled 
1: Uploading parameter 
2: Downloading parameters 
3: Downloading parameters (except 
the motor parameters) 
Note: The drive parameters will not be 
uploaded/downloaded 
1 0 × √ ×