72
P03.18
Stator
resistance
of motor 2
Stator
resistance
R1
0.000~65.000 0.001
Depend
ing on
model
√ √ ×
P03.19
Leakage
inductance
of motor 2
Leakage
inductance
of motor 2 X
0.0~650.00 0.01
Depend
ing on
model
√ √ ×
P03.20
Rotator
resistance
of motor 2
Rotator
resistance of
motor 2 R2
0.000~65.000 0.001
Depend
ing on
model
√ √ ×
P03.21
Mutual
inductance
of motor 2
Mutual
inductance
of motor 2
Xm
0.0~650.00 0.01
Depend
ing on
model
√ √ ×
P03.22
No-load
current (I0)
of motor 2
No-load
current (I
0)
0.1~999.9A 0.1A
Depend
ing on
model
√ √ ×
P03.23
Overload
protection
factor of
motor 2
Overload
protection
factor of
motor 2
20.0~110.0%
Set action level (%) = motor rated
current/ drive rated current × 100
Low speed compensation actual action
level = set action level × (output
frequency/ 30HZ × 45 + +55)
Actual converted current of overload
protection = sampling current/overload
protection action level
0.1% 100.0% √ √ ×
P03.24
Parameter
auto-tuning
Parameter
auto-tuning
0: Disabled
1: Enabled (motor in static status)
2: Enabled (motor in rotate status)
3: Reserved (according to the
nameplate setting)
1 0 √ √ ×
P03.25~
P03.28
Reserved
Group P07: VF control parameters
P07.00
Motor 1 V/F
curve
setting
Motor 1 V/F
curve setting
0: User-customized V/F curve
1~16:Reserved
17: 2 times power curve
18: 1.7 times power curve
19: 1.2 times power curve
1 0 × √ ×
P07.01
Motor 1 V/F
frequency 3
Motor 1 V/F
frequency 3
P07.03~P03.03 0.01Hz 0.00Hz × √ ×
P07.02
Motor 1 V/F
voltage 3
Motor 1 V/F
voltage 3
P07.04~100.0% 0.1% 0.0% × √ ×
P07.03
Motor 1 V/F
frequency 2
Motor 1 V/F
frequency 2
P07.05 ~P07.01 0.01Hz 0.00Hz × √ ×
P07.04
Motor 1 V/F
voltage 2
Motor 1 V/F
voltage 2
P07.06~P07.02 0.1% 0.0% × √ ×
P07.05
Motor 1 V/F Motor 1 V/F
0.00~P07.03 0.01Hz 0.00Hz × √ ×