EasyManua.ls Logo

Metasys TC-9100 Series - Page 55

Metasys TC-9100 Series
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Bulletin—TC-9100 Universal Controller 55
TB1 TB2
TM-9180
Module
TC-9100
Controller
14 15 22 24
+15V
CLOCK
T/R
COM
14
15 20
21/
24
22
23
1 2 3 4 5 6
Blue
White
Red
}
utc0tm
Extension Cable
Code: DR-9100-8914
To Service Module
Socket in TC-9100
Controller
Service Module
Socket
Max. 50 m
Min. 0.8-mm
diameter wire
Figure 24: Wiring to TM-9180 Room Command Module
Note: Set JP3 to left position. See Jumper and Switch Settings.
TS-9100
Sensor
RS-1140
Module
TC-9100
Controller
50 51 52 53 54 55
AI3 AI4
+15V+15V
COMCOM
1 2 4
+15V
TEMP
(0-10V)
TEMP
(0-10V)
COM
1 3 4
+15V COM
utc0aiw
Max. 50 m
Min. 0.8-mm
diameter wire
Figure 25: Wiring to Analog Inputs