64 Technical Bulletin—TC-9100 Universal Controller
Item Type MEM R/W Tag Description
Hex Dec
1E 30 2 Bytes V R ALR Analog Input Alarm Status
X1=1 AIH1 Analog Input 1 High Alarm
X2=1 AIL1 Analog Input 1 Low Alarm
X3=1 AIH2 Analog Input 2 High Alarm
X4=1 AIL2 Analog Input 2 Low Alarm
X5=1 AIH3 Analog Input 3 High Alarm
X6=1 AIL3 Analog Input 3 Low Alarm
X7=1 AIH4 Analog Input 4 High Alarm
X8=1 AIL4 Analog Input 4 Low Alarm
X16...X9 not used
1F 31 1 Byte V R LOS Logic Output Status
X1=1 DO3 Digital Output 3 On
X2=1 DO4 Digital Output 4 On
X3=1 DO5 Digital Output 5 On
X4=1 DO6 Digital Output 6 On
X5=1 DO7 Digital Output 7 On
X6=1 DO1 Digital Output 1 On
X7=1 DO2 Digital Output 2 On
X8 not used
20 32 1 Byte V R ROS TC-9100 Operating Status
X2 X1 MODS Mode Status
=00 NIGHT Mode
=01 STANDBY Mode
=10 COMFORT Mode
=11 OFF Mode
X3=1 MODT Temporary Mode
X4=1 ALT Alternate Mode
X5=1 Supervisory System Active
X6=1 WIN Window Open
X7=1 OCC Occupancy
X8=1 AIRQ Air Quality/Override
X8=1 AIRQ Air Quality/Override