ADMIN - Alarms
PTP Leap 59: Leap second deletion is pending. The last minute of the day will have 59
seconds.
PTP Leap 61: Leap second insertion is pending. The last minute of the day will have 61
seconds.
PTP Clock Accuracy: The system is not locked to a reference source and is not within the hol-
dover specifications. The PTP Clock Class is 52.
PTP Queue Reset: A PTP queue has filled up and was flushed.
PTP Daemon Reinit: The PTP daemon was overloaded and reinitialized.
FactoryDefaultSettingsforAlarms
Name
Auto
Clear
Severity
Send
Trap
Write
Log
Send
Email
NTP System Peer Change Notify
Y
NTP Stratum Change
Y Major Y Y Y
NTP Leap Change
Y
Notify
Y
System Network
Y
Notify
Y
System Upgrade
Minor Y Y Y
System Config Change Notify
Y
System Health
Y Major Y Y Y
System Up/Down
Y Minor Y Y Y
System Authentication
Y
Notify
Y
Timing No Source
Y Major Y Y Y
Timing GPS
1
Source
Y Major Y Y Y
Timing Timecode Source
Y
Notify
Y
Timing PPS Source
Y
Notify
Y
Timing 10MHz Source
Y
Notify
Y
Timing GPS Antenna Short
Y Major Y Y Y
Timing GPS Antenna Open
Y Major Y Y Y
Timing Oscillator DAC Range Notify
Y
Timing Rubidium Lock Notify
Y
Timing Oscillator Unlock Notify
Y
Timing Source Change Notify
Y
Timing Source Lower Accuracy Input Notify
Y
Timing PLL Unlock
Y
Notify
Y
Timing Quality 1e-6
Y
Notify
Y
Timing Quality 1e-5
Y
Notify
Y
Timing Quality 1e-4
Y
Notify
Y
Timing Quality 1e-3
Y
Notify
Y
1
The SyncServer S350i does not include a GPS receiver.
997-01520-02 Rev. F1.......................................................................... Page 89