MCAC-CTSM-2014-03 DX type water-cooled screw chiller (PCB Control)
25
For system, Qg is calculated according to the lowest load so that it operates steadily.
It can also calculated according to 0.5Q(50%). T takes 8 minutes, the shortest time that the unit
running. That is 480s. Cp=4.18kj/kg, ▽t =5℃
According to the above formula, the result is as following:
W=0.5Q*480/(4.18*5)=11.48Q kg
Note:
The above formula is only for reference, different factor should be adopted to suit for different condition.
8. Unit sound levels
10. Recommend breaker current
All units has equipped with breaker with user. All refrigerant circuit repairs must be carried out by a
trained, qualified and skilled technician and following local regulations
Midea recommended breaker current for units as follow: