DX type water-cooled screw chiller (PCB Control) MCAC-CTSM-2014-03
40
EXV controller is started by main base controller.it detects suction pressure and suction temperature
and calculate suction superheat. Then it controls EXV opening depending on superheat. If it is wrong,
EXV will output alarm signal to main base controller.
b. Controller display
The interface of EXV controller cannot display and set parameter on unit, only running status display.
If parameter needs to be displayed and set. Interface should be changed.
LED
Light
Extinguish
Flicker
NET
Can be
connected to
the network
Not
connected
Communication
failure
OPEN
Open the valve
-
Disable the drive
CLOSE
Close the valve
-
Disable the drive
Activate the
alarm
-
-
Drive power
The drive is
not connected
to power
supply
-
24V AC
Suction pressure
transmitter
Suction temp.
thermistor
Start/stop relay
From controller
EXV
CAREL EXV controller EVD
Alarm output
to controller