15
8.2 Application 2
ROOM THERMOSTAT Control for Space heating or cooling need to be set on the user interface. It can be set 
in three ways: MODE SET/ONE ZONE/DOUBLE ZONE. The molobloc can be connected to a high voltage room 
thermostat and a low voltage room thermostat. A hydraulic adapter box can also be connected. Another six 
thermostats can be connected to the hydraulic adapter box. Please refer to 9.7.6/6. “FOR ROOM THERMOSTAT” for 
wiring. (see 10.6.6 "ROOM THERMOSTAT" for setting) 
 
Code  Assembly unit  Code  Assembly unit 
1  Main unit   14  Shut-off valve (Field supply) 
    15  Filling valve (Field supply) 2
 
User interface
  16  Drainage valve (Field supply) 
4
 
Balance tank
 
(Field
 
supply)
 
19  Collector/distributor (Field supply) 
4.1
 
Automatic air purge valve
  21  Hydraulic adapter box (Optional) 
4.2
 
Drainage valve
 
RT 1…7   Low voltage room thermostat (Field supply) 
5
 
P_o:  Outside  circulation  pump
 
(Field
 
supply)
 
RT8
 
High voltage
 
 room
 
 thermostat
 
 (Field
 
 supply
 )
 
10
 
Expansion vessel 
(Field
 
supply)
 
FHL 
1…n 
Floor heating loop (Field supply) 
12
 
Filter (Accessory
)
 
Space heating
 
One zone control: the unit ON/OFF is controlled by the room thermostat, cooling or heating mode and outlet 
water temperature are set on the user interface. System is ON when any “HL” of all the thermostats closes. When 
all “HL” open, system turns OFF. 
 
The circulation pumps operation
 
When the system is ON, which means any “HL” of all the thermostats closes, P_o starts running; When the 
system is OFF, which means all “HL” close, P_o stops running. 
5
4
4.2
4.1
10
FHL1 FHL2 FHLn
19
8.2.1 One zone control 
Outdoor
1
Indoor
RT2 RT3
21
RT4
RT5
RT7
RT6
RT8
RT1
Modbus
15
16
14
12
14
2
16