18
9 OVERVIEW OF THE UNIT
9.1 Disassembling the unit
WARNING
Switch off all power — i.e. unit power supply and backup heater and domestic hot water tank power supply (if 
applicable) — before removing doors 1 and 2.
Parts inside the unit may be hot.
Door 1
To access to the compressor and 
electrical parts.
Door 1
Door 2
To access to the hydraulic 
compartment and electrical parts.
To access to the compressor and 
electrical parts and  hydraulic 
compartment 
4/6kW
8/10/12/14/16kW
1 1 2
The floor heating loops require a lower water temperature in heating mode compared to radiators. To achieve 
these two set points, a mixing station is used to adapt the water temperature according to requirements of the floor 
heating loops. The radiators are directly connected to the unit water circuit and the floor heating loops are after 
the mixing station. The mixing station is controlled by the unit. 
1) Make sure to connect the SV2/SV3 terminals in the wired controller correctly,please refer to 9.7.6/2) for 3-way 
valve SV1,SV2,SV3.
2) Thermostat wires to the correct terminals and to configure the ROOM THERMOSTAT in the wired controller 
correctly . Wiring of the room thermostat should follow method A/B/C as described in 9.7.6 "Connection for other 
components / 6) For room thermostat". 
CAUTION
NOTE
1) Zone 2 can only operate in heating mode. When cooling mode is set on user interface and zone 1 is OFF, “CL” 
in zone 2 closes, system still keeps “OFF”. While installation, the wiring of thermostats for zone 1 and zone 2 
must be correct.  
2) Drainage valve(9) must be installed at the lowest position of the piping system.
The Balance tank volume requirement:
NO.   model   Balance tank (L) 
1  4~10 kW  ≥25 
2  12~16 kW  ≥40