12.4 t_DRYUP The day for w arming up during floor drying up 8 4 15 1 DAY
12.5 t_HIGHPEAK
The continue days in high temperature during floor
drying up
5 3 7 1 DAY
12.6 t_DRYD
The day of dropping temperature during floor drying
up
5 4 15 1 DAY
12.7 T_DRYPEAK
The target peak temperature of w ater flow during
floor drying up
45 30 55 1 °C
12.8 START TIME The start time of floor drying up
Hour
the
present
time(not on
the hour +1,
on the hour
+2)
Minute:00
0:00 23:30 1/30 h/min
12.9 START DATE The start date of floor drying up
The present
date
1/1/2000 31/12/2099 1/1/2001 d/m/y
13.1
AUTO RESTART
COOL/HEAT MODE
Enable or disable the auto restart cooloing/heating
mode. 0=NON,1=YES
1 0 1 1 /
13.2
AUTO RESTART DHW
MODE
Enable or disable the auto restart DHW mode.
0=NON,1=YES
1 0 1 1 /
14.1 POWER INPUT LIMITATION
The type of pow er input limitation, 0=NON,
1~8=TYPE 1~8
0 0 8 1 /
15.1 ON/OFFM1 M2
Define the function of the M1M2 sw itch;
0= REMOTE ON/OFF,1= TBH ON/OFF,2= AHS ON/OFF
0 0 2 1 /
15.2 SMART GRID
Enable or disable the SMART GRID;
0=NON,1=YES
0 0 1 1 /
15.3 T1bTw 2
Enable or disable the T1b(Tw 2) ;
0=NON,1=YES
0 0 1 1 /
15.4 Tbt1
Enable or disable the Tbt1;
0=NON,1=YES
0 0 1 1 /
15.5 Tbt2
Enable or disable the Tbt2;
0=NON,1=YES
0 0 1 1 /
15.6 Ta
Enable or disable the Ta;
0=NON,1=YES
0 0 1 1 /
15.7 SOLAR INPUT
Choose the SOLAR INPUT;
0=NON,1=CN18Tsolar,2=CN11SL1SL2
0 0 2 1 /
15.8 F-PIPE LENGTH
Choose the total length of the liquid pipe(F-PIPE
LENGTH);
0=F-PIPE LENGTH10m,1=F-PIPE LENGTH10m
0 0 1 1 /
15.9 dTbt2 The temperature difference for starting the unit(Tbt2) 15 0 50 1
15.10 RT/Ta_PCB
Enable or disable the RT/Ta_PCB;
0=NON,1=YES
0 0 1 1 /
16.1 PER_START Start-up percentage of multiple units 10 10 100 10 %
16.2 TIME_ADJUST Adjustment time of adding and subtracting units 5 1 60 1 MIN
16.3 ADDRESS RESET Reset the address code of the unit FF 0 15 1 /
17.1 HMI SET
Choose the HMI;
0=MASTER,1=SLAVE
0 0 1 1 /
17.2 HMI ADDRESS FOR BMS Set the HMI address code for BMS 1 1 16 1 /