68
ERROR 
CODE
MALFUNCTION 
OR PROTECTION
FAILURE CAUSE 
AND CORRECTIVE ACTION
1. The  T3 sensor connector is loosen. Reconnect it. 
2.The T3 sensor connector is wet or there is water in. remove 
the water, make the connector dry. Add waterproof adhesive 
3. The T3 sensor failure, change a new sensor. 
The condenser outlet 
refrigerant temperature sensor 
(T3)error.
1.Check the power supply cables should be conneted 
stable,aviod phase loss.
2.Check whether the sequence of neutral wire and live wire are 
connected reversely.
Phase loss or neutral wire and 
live wire are connected 
reversely(only for three phase 
unit)
1. The  T4 sensor connector is loosen. Reconnect it. 
2.The T4 sensor connector is wet or there is water in. remove 
the water, make the connector dry. Add waterproof adhesive 
3. The  T4 sensor failure, change a new sensor.
The ambient temperature 
sensor (T4) error.
1. The Th sensor connector is loosen. Re connect it. 
2.The Th sensor connector is wet or there is water in. remove 
the water, make the connector dry. Add waterproof adhesive 
3. The Th sensor failure, change a new sensor.
Suction temperature 
sensor(Th) error
1.wire doesn’t connect between main control board PCB B and 
main control board of indoor unit. connect the wire. 
2. Whether there is a high magnetic field or high power 
interfere, such as lifts, large power transformers, etc.. To add a 
barrier to protect the unit or to move the unit to the other place.
Communication fault between 
indoor unit and outdoor unit
1. The Tp sensor connector is loosen. Re connect it. 
2.The Tp sensor connector is wet or there is water in. remove 
the water, make the connector dry. Add waterproof adhesive 
3. The Tp sensor failure, change a new sensor.
Discharge temperature 
sensor(Tp) error
1. Whether there is power connected to the PCB and driven 
board. Check the inverter module PCB indicator light is on or 
off. If Light is off, reconnect the power supply wire.
2.if light is on, check the wire connection between inverter 
module PCB and main control board PCB, if the wire loosen or 
broken, reconnect the wire or change a new wire.
3. Replace a new main PCB and driven board in turn.
Communication error between 
inverter module PCB A and 
main control board PCB B
Same to P6
Three times P6 protect