49
Front Panel Menu Operation
5.7.3 Silent Test (Single Node System)
During this test, alarm activation of any input device activates all signals for one half second.
Trouble activation on any input device activates all signals continuously for one second. If
audio amplifier is configured for alarm and trouble events, it sounds words “Alarm” and
“Trouble” respectively.
Step 1: Select one man test
1. Use and to scroll the cursor to “One
Man”.
2. Press when the cursor flashes beside “One
Man” to select the One Man Walk Test.
Step 2: Select Silent Test
1. Use and to scroll the cursor and select
“Silent Test”.
2. Press when the cursor flashes beside “Silent
Test” to select the Silent Test.
Step 3: Select duration of the walk test
1. The default duration of Walk Test is 6 hours. To
choose another time duration, use the and
to scroll the cursor to the desired duration
time. Valid range is from 1 hour to 12 hours.
2. Press to select the Walk Test duration.
Step 4: Start the walk test
Start or Resume Test for device inspection.
1. Select Start to begin a Walk Test.
2. Select Resume to continue the Walk Test.
As the test runs, the counts of Alarms and Troubles
increase as they are recorded (logged) during the
Audible Test.
Press to end the walk test at any time.
- Walktest -
1
One Man
2 Walk Test Report
- Walktest -
1 Audible Test
2 Silent Test
- Walktest -
Timeout 6 hours
- Walktest -
1 Start
2 Resume