Introduction
TX3 Touch Screen Installation Manual 11
any device on the RS-485 network (using USB, a modem, or the COM port), you
can also connect to and configure any other device on the RS-485 network using
the TX3 Configurator.
Figure 1. TX3 devices on an RS-485 network
Figure 2 shows a configuration with TX3 devices connected to an Ethernet TCP/
IP network. This configuration removes the 63 device limitation that you have on
an RS-485 network. The devices connected to an Ethernet TCP/IP network are
called Master Nodes. If you connect to the TCP/IP network with the TX3
Configurator, you can connect to and configure any of the Master Nodes on the
Ethernet TCP/IP network. If you connect directly to one of the Master Nodes
using USB, a modem, or a COM port, you will be able to configure that device
but not any other device.
RS-485 Network
Card Reader B
Card Reader A
Card Access ControllerTouch Screen Unit
Elevator Restriction Unit

Table of Contents